Back to Study material
EM1


Unit 1


Transformers

Q.1) Derive the emf equation of the transformer.

Sol:
An ideal transformer has no losses i.e. its winding having no magnetic leakage and no ohmic resistance. Hence, an ideal transformer has only two purely inductive coils wound on a loss-free core.

Fig. Ideal Transformer

For above transformer when secondary is open and primary is having input sinusoidal voltage V1. An alternating -current flows due to difference in potential. As primary coil is purely inductive so, Iµ current is drawn through it. This current is very small and logs V1 by 900.

The current Iµ produces magnetic flux φ and hence are in same phase. The flux is linked with both the windings and hence, self-induced emf is produced E1 which is equal and opposite of V1. Similarly, E2 is induced in secondary which is mutually induced emf E2 is proportional to rate of change of flux and number of secondary windings.


The phasor is shown below.

Fig. Phasor for Ideal Transformer

Emf Equation of Transformer:

N1 = No of primary turns

N2 = No of secondary turns

Φm = max flux in cone (wb)

Φm = Bm x A

f = Frequency of input(ac) Hz

 

Average rate of change of flux

= Φm / ¼ 

= 4 ΦmF volts

Average emf per turn = 4F ΦmV

 

As Φ varies sinusoidally rms value of induced emf is given as

Form factor = r.m.s value / average value = 1.11

r.m.s value of emf/turn = 1.11 x 4f Φm

= 4.44 f Φm volt

 

r.m.s value of induced emf in primary winding

= (induced emf/turn) x No of primary turns

E1 = 4.44 fN1 Φm

E1 = 4.44 fN1BmA

r.m.s emf induced in secondary

E2 = 4.44 fN2 Φm

E2 = 4.44 fN2BmA

E1/E2 = N1/N2 = K

K – voltage transformation

 

(i). If N2 > N1 i.e K > 1 STEP UP TRASFORMER

(II). If N1 > N2 i.e K<1 STEP DOWN TRASFORMER

 

FOR Ideal Transformer

V1 I1 = V2 I2 = 1/K

Hence, current is inversely proportional to the voltage transformation ratio.

 

Q.2) Describe in brief the open circuit and short circuit test of transformer?

Sol:

(1) OPEN CIRCUIT TEST:

Basically, these tests are performed to find the basic parameters of transformers. The open circuit test is performed to determine no-load loss (core loss) and no-load current I0 which is helpful in finding X0 and R0.


Fig. Open Circuit Test

In this test the high voltage winding is left open and the other is connected to supply.

A wattmeter W, voltmeter V and an Ammeter A are connected to L.V. Winding.

Due to applied voltage in primary, flux is set up in core, and hence normal iron loss occurs. This is recorded in Wattmeter. The current I0 is measured by Ammeter A.

Wattmeter reading represents core loss under no-load condition.

The wattmeter reading will be given as

W = V1 I0 cos φ0

Iµ = I0 Sin φ0

Iw = I0 cos φ0

X0 = V1/Iµ, R0 = V1/Iw

At no load I0 ≈ Iµ

I0 = V1 Y0

Y0 – Exciting Admittance

W = V21 G0

G0 – Exciting conductance

B0 = √ Y20 – G20

B0 – Exciting susceptance

 

(2) SHORT CIRCUIT TEST:

This test is used to determine

(i). Equivalent Impedance (Z01, Z02), leakage reactances (X01 or X02), Total resistance (R01, R02).

(ii). Cu losses are also calculated at full load.

(iii). The regulation of transformer can be determined as Z01, Z02 can be calculated.


Here low voltage is short circuited. And the supply is through high voltage (primary here).

As applied voltage is small, hence the flux φ induced is also small.

As core losses are very small, the wattmeter reading is the cu-loss at full load for whole transformer.


The equivalent circuit is shown below,

 

Z01 = Vsc/I1

Vsc = voltage to circulate rated load current

W = I21 R01

R01 = W / I21

X01 = √ Z201 – R201

R’2 = R01 – R1

 

Q.3) The core of a 110 KVA, 10,000/500v, 50 Hz, 1-Φ core type transformer has a cross section of 18 cm x 18 cm. Find the number of HV and LV turns per phase and the emf per turn if the maximum core density does not exceed 1.3 tesla. Assume a stacking factor pf 0.9.

Sol: Bm= 1.3T

Area = (0.18 x 0.18) = 0.032m2

Emf induced in primary

E1 = 4.44 fN1BmA

10000=4.44 x 50 x N1 x 1.3 x 0.032

N1=1082.8

Emf induced in secondary

E2 = 4.44 fN2BmA

500= 4.44 x 50 x N2 x 1.3 x 0.032

N2= 54.14

i)                   The number of turns is N1=1082.8 and N2= 54.14

Ii)                 Emf per turn = E1/E2 = N1/N2 = K

=10000/1082=9.24V or 500/54.14=9.23V

 

Q.4) A 1-Φ transformer has 400 turns in primary and 110 turns in the secondary. The cross-sectional area of the secondary. The cross-sectional area of the core is 80cm2. If the primary winding is connected to the 50 Hz supply at 500V. Calculate peak flux density in core.

Sol: As we know Emf induced in primary

E1 = 4.44 fN1BmA

500 = 4.44 x 50 x 400 x Bm x (80x10‑4)

Bm=0.704Wb/m2

 

Q.5) A 2000/200v transformer draws a no-load primary current of 0.6A and absorbs 360 watts find the magnetising and iron loss currents.

Sol: Iron loss current = = 360/2000=0.18A

I20 = I2w + I2µ

Magnetising component Iµ = √I20 – I2w

= √ (0.6)2 – (0.18)2

Iµ = 0.57 A

 

Q.6) A 2200/250 V transformer takes 0.7A at a p.f of 0.4 0n open circuit. Find the magnetising and working component of no load primary current?

Sol: I0= 0.7A

Cosφ0=0.4

Iw= I0 cosφ0

Iw=0.7 x 0.4=0.28A

Magnetising component Iµ = √I20 – I2w

= √ (0.7)2 – (0.280)2

Iµ = 0.64 A

 

Q.7) A single phase transformer has 400 turns in primary and 1000 turns in secondary. The cross-sectional area is 80 cm2. If primary is connected to 50hz at 500V. Voltage induced in secondary?

Sol: As we know Emf induced in primary

E1 = 4.44 fN1BmA

500= 4.44x50x1000xBmx(80x10-4)

Bm= 0.28Wb/m2

The voltage induced in secondary is given as

E1/E2 = N1/N2 = K

E2=1000x500/400=1250V

 

Q.8) A 200 KVA, 1200/200v, 50 Hz, 1-Φ transformer has a leakage impedance of (0.1 + 0.30) Ω for the HV winding and (0.005 + 0.015) Ω for the LV winding. Find the equivalent winding resistance, reactance and impedance referred to the HV and LV side.

Sol: The Turn ratio is given as E1/E2 = N1/N2 = K

K=6

i)                   Referring to High Voltage Side

Resistance = R1+K2R2= 0.1+ 62 x 0.005 =0.28ohm

Reactance = X1+K2X2= 0.30+ 62 x0.015 = 0.84ohm

Impedance = √0.282 +0.842

=0.880hm

Ii)                 Referring to Low voltage sides

Resistance= R1/ K2+R2= (0.1/62) + 0.005=0.007ohm

Reactance = Reactance HV side/ K2=0.84/62=0.013ohm

Impedance = Impedance referring HV/ K2= 0.88/62 = 0.024ohm

 

Q.9) When a transformer is connected to a 1200v,50Hz supply the core loss is 900 W, of which 600 is hysteresis and 350 W is eddy current loss. If the applied voltage is raised to 2000V and frequency to 100 Hz. Find new core losses.

Sol: Hysteresis Loss (Wh) α f =P f

Eddy current Loss (We) α P f2 = Q f

The emf equation of transformer is given as E= 4.44fNBmaxA

Bmax α E/f

So, the above equations become Wh = P (E/f)2 f = P E1.6 f-0.6

600= P x 12001.6 x 50-0.6

P=0.074

The eddy current loss               We= Q (E/f)2 f2 = QE2

350=Q x 12002

Q=0.243 x 10-3

Now the applied voltage is raised to 2000V so finding new losses with above found P and Q

Wh = P E1.6 f-0.6 = 0.074 x 20001.6 x 100-0.6 = 893.06W

We= QE2 = 0.243 x 10-3 x 20002 = 972 W

 

Q.10) A short circuit test when performed on HV side of a 12kVA,2000/400v, 1-Φ transformer the data is:50v, 3A, 100W. If the LV side is delivering full load current at 0.8 p.f and at400v, find the Voltage applied to HV side.

Sol:   As the test is done from HV side which is primary side

Z01=50/3 = 16.67ohm

R01= 100/32 = 11.11ohm

X01= 16.672 – 11.112 = 12.42ohm

I1= 12x1000/2000 = 6A

Voltage drop referred to primary is E = I1(R01 cosφ + X01 sinφ)

= 6 (11.11 x 0.8 + 12.42 x 0.6)

E = 98.04V

 

Q.11) A transformer has cu loss of 1.5% and the reactance drop of 3.2% when tested at full load. Calculate its full load regulation at unity power factor.

Sol: Approx. Voltage regulation at unity p.f (full load) = 0.015 cos φ + 0.032 sin φ= 0.015 = 1.5%

Approx. Voltage regulation at 0.08 lagging p.f = 0.015 x 0.8 + 0.032 x 0.6 = 0.032=3.2%

Approx. Voltage regulation at 0.08 leading p.f = 0.015 x 0.8 – 0.032 x 0.6

= 7.2x10-3= -0.72%

 

Q.12) A 20kVA 440/220V 1-phase transformer 50Hz has iron loss of 289W. The Cu losses found to be 60W and delivers half of full load current. Determine percentage of full load when the efficiency will be maximum?

Sol: =

Full load Cu loss = 22 x 100 = 400W

= = = 0.85

Hence, efficiency will be maximum at 85%

 

Q.13) A 20kVA, 1-Φ transformer,50Hz,500/250v gave following results

OC test (LV side): 230v,2.8A,200W

SC test (LV side): 15v,30A,300W

Calculate the efficiency at full load 0.8 p.f lagging.

Sol: Full load current = 20000/230 = 86.96A

SC current is measured till 30A on low voltage side.

I2R losses 40A n low voltage side = (40/30)2 x 300 = 533.3W

Iron loss for OC test = 200W

Full load output at p.f 0.8 = 20000 x 0.8 =16kW

Efficiency = {(16x1000)/[16000+200+533.33]} = 0.956 = 95.6%

 

Q.14) Explain in detail about the losses that occur in transformer?

Sol:

Core or Iron Loss:

This includes both hysteresis loss and eddy current loss. Iron or core loss is found from open circuit test.

Hysteresis Loss(Wh) = nB1.6max f V Watt

Eddy current Loss(We) = P B2max f2 t2 Watt

 

Copper Loss:

This is due to ohmic resistance of the transformer windings.

Total cu loss = I21 R1 + I22 R2

= I21 R01 + I22 R02

Cu loss α I2

The value of cu loss is found from short-circuit test.

 

Q15) Derive the condition for maximum transformer efficiency.

Sol:

Condition for maximum efficiency:

For n to be maximum dn/dI1 = 0

(Ww) cu loss = I21 R01 or I22 R02

Iron loss = Hysteresis loss + Eddy current loss

= Wn + We = Wi

n = Input – losses/Input

Primary Input = V1I1 Cosφ1

n = V1 I1 Cosφ1 – losses/V1 I1 cos φ1

n = V1 I1 cos φ1 – I21 R01 – Wi / V1I1 cosφ1

= 1 – I1R01/V1cosφ1 – Wi/V1I1cosφ1

Differentiating w.r.t I1 both sides of above equation we have

Dn/dI1 = 0 – R01/V1cosφ1 + Wi/V1I21 Cosφ1

For max value dn/dI1 = 0

R01/V1cosφ1 = Wi/V1I21 cosφ1

Wi = I21 = I21 R01

Hence,

Wi = Wcu

Iron loss = copper loss

The value of output current for maximum efficiency will be

I2 = √Wi/R02

The maximum efficiency can also be given as,

nmax = full load x √ Iron loss / F.L .cu loss

Or

nmax = R’ x full load KVA x pf / R’ x full load KVA x pf + Wi + Wcu x 100

R’ = ratio of actual to full load KVA

Wi = iron loss (KW)

Wcu = copper loss (KW)